Chemical Storage
Minimum Specifications for Agri-Chemical Storage
Provide and deliver one pre-engineered, portable hazardous material storage building to selected location. This building shall be FM approved and suitable for storage of combustible, flammable liquids and other hazardous materials. Building shall not require specific foundations or supports. All materials used in construction must be new and unused. Use of wood in construction is unacceptable. Manufacturing quality compliance shall be in accordance with ASTM, AISI, and AWS materials and fabrication standards. The building must meet the model building codes, model fire codes, safety and environmental regulations:
Current Additions:
International Building Codes (IBC)
BOCA National Building Code
Standard Building Code
Uniform Fire Code
BOCA National Fire Prevention Code
Standard National Fire Prevention Code
BOCA Building Officials and Code Administrators
National Electric Code (NEC/NFPA 70)
OHSA (29 CFR)
EPA (40 CFR)
California Administrative Code
NFPA - National Fire Protection Assoc.
AWS - American Welding Society
AISC – American Institute of Steel Construction
ANSI - American National Standards Institute
ASTM - American Society For Testing and Material
USPC – United States Product Code
Download Agri-Chemical Storage Design Specifications
Factory Mutual (FM) – All Standard chemical storage buildings from Securall are FM Approvoed (#6049). Walls are Non-Fire Rated, 2-Hour Fire Rated, or 4-Hour Fire Rated (Check with Local authority having Jurisdiction for Correct wall rating needed). Roof to be FM Approved Non-Fire Rated, 1.5-Hour Fire Rated, or 3-Hour Fire Rated. | |
Underwriters Laboratories (UL) – Securall fire doors and window frames are UL Listed (#R18951). Securall Swinging doors are UL Listed (#R18828) and certified in Canada. | |
What are SMaRT Sustainable Products? They are independently certified products deemed to be the best option for the overall sustainability of the environment. |
Structural Features
Standard Design Loads
Roof Snow Load: Up to 70 PSF
Wind Load: Min. 90 mph (B1200 and smaller), Min. 170 mph (B1600 and larger)-See Wind Shear Chart
Live Floor Load: 250 psf standard – 500 psf available
Seismic Condition: Zone 4
Exterior Wall Construction for AG200-AG1200
Provide noncombustible walls constructed from heavy gauge steel to provide maximum durability, weather resistance, and rigidity.
Exterior Wall Construction for AG1600-AG8000
Provide noncombustible walls constructed from heavy gauge steel to provide maximum durability, weather resistance, and rigidity.
Door for AG200-AG400
Provide one 42” wide x 62.5” high door to facilitate the unloading and loading of hazardous material within the building. Installed with a UL Classified commercial grade keyed lockset. The door shall serve as personnel entrance and exit.
Door for AG600-AG1200
Provide one 42” wide x 80” high door to facilitate the unloading and loading of hazardous material within the building. Installed with a UL Classified commercial grade keyed lockset. The door shall serve as personnel entrance and exit.
Door for AG1600-AG8000
Provide one 60” wide x 80” high double door to facilitate the unloading and loading of hazardous material within the building. Installed with a UL Classified commercial grade keyed lockset. The double door shall have one active leaf to serve as personnel entrance and exit. The active leaf must be equipped with a door closer. Available as an upgrade on models B600 through B1200.
Sump Containment
Provide built-in 7-inch high spill containment sump with chemical resistant coating. Sump construction to be weather proof, noncombustible utilizing continuously welded steel sheets for maximum spill containment protection. Mechanical fastener penetrations cannot be used on sump wall skins. Sump capacity to be a minimum 25% of total storage capacity of the building.
Steel Floor Planking
Floor planking above sump area shall be galvanized steel for maximum corrosion resistance. Floor planking must be designed to sustain a minimum uniformly distributed load of 250 pounds per square foot (psf). Floor planking supports must be removable to facilitate sump cleaning in the event of a spill. Permanent or welded in place floor supports are unacceptable.
Building Base
Provide open channel design to allow visual inspection under building. Crane/forklift opening to be provided for ease in off loading and relocation.
Interior Finish
Finish on ceiling, walls, and sump floor with a two-part chemical resistant gray aliphatic polyurethane. Able to withstand salt spray/chemical rub and durable to impact damage.
Exterior Finish
Finish on roof, walls, and doors surfaces with a two-part chemical resistant gray aliphatic polyurethane. UV protection. Able to withstand salt spray/chemical rub and durable to impact damage.
Signs/Labeling
Provide one permanent all metal DOT hazard classification placard with rustproof aluminum holder and one pressure sensitive NFPA 704 hazard rating sign on door.
Anchoring
7 gauge angle with 7/8” hole welded to building for wind and seismic anchoring.
Signs/Labeling
Provide one permanent all metal DOT hazard classification placard with rustproof aluminum holder and one pressure sensitive NFPA 704 hazard rating sign on door.
Air Inlet Vents
Provide air inlet vents for natural ventilation. Natural ventilation shall provide a rate of 1cubic foot per min per square foot of floor space. Each vent to be equipped with an exterior louver for optimum airflow and preclusion of bird and animal entry.
Fire Rating
If a fire rated building is required, it must have an FM Approved Fire Rated Wall and Roof Design. Wall and roof should be tested at Intertek Testing Laboratories. Wall ratings are either 2 or 4 hour fire rated (Check with your local authority having jurisdiction for correct wall/roof rating needed). Roof ratings are either 1.5 or 3 hour fire rated. Building will consist of multiple layers of ¾” Gypsum Ultracode Wallboard. Air inlet vents will have UL Listed and Labeled fire dampers with louvers. Dampers have a galvanized steel frame, curtain-style galvanized steel blades and a UL Listed 165 degree fusible link.
Electrical System
Provide a pre-wired electrical system including necessary breaker panel, relays, and switches. All interior electrical components must be rated for class 1, division 1 or division 2, subtle for hazardous locations. Pre-wired electrical systems to include one exterior NEMA 3R load center with appropriate circuit breakers.
Grounding
Provide interior and exterior grounding lugs to building. Exterior optional – grounding kit with ½” dia. X 8’ long copper plated ground rod, ½” dia. Copper alloy rod clamp, and 10’ - #6 bare copper wire. Conforms to OSHA requirements 1910.106. Building to be grounded per local building codes.
Interior Lighting
Provide dust/moisture resistant fluorescent light(s) ceiling mount type and rated for wet locations. Light fixture to be activated by one exterior light switch suitable for outdoor locations. Electrical requirements are 120 volt, single phase, .73 amps, 40 watt, UL Listed.
Exterior Lighting
Provide one exterior moisture resistant light fixture with photocell rated for outdoor locations. Light fixture shall be fully enclosed with a gasket between the die-cast aluminum housing and lens. A lens guard shall protect shall protect the lens. Electrical requirements are 120 volt, single phase, 1.25 amps, 150 watt, UL Listed.
Receptacles
Provide one exterior GFI receptacle located in close proximity to load center. Electrical requirements are 120 volt, single phase, 20 amps, UL Listed.
Fire Suppression Systems (Optional)
Fire Sprinkler Assembly
Provide fire sprinkler piping subassembly equipped with a minimum of one sprinkler head and an exterior NPT fitting.
Dry Chemical Fire Suppression System
Provide one pre-engineered dry chemical fire suppression system rated for Class A, B, and C fires. Systems to include fusible link detection for automatic actuation, audible alarm, and exterior manual activation. System to include interior nozzle system for total flooding application. Dry chemical agent tank and releasing device must be housed inside an exterior tamperproof enclosure per the requirements of NFPA 17. System to be equipped with automatic ventilation system shutdown upon system actuation. SECURALL® is a certified Ansul installer.
Heating, Ventilating, and Air Conditioning System (Optional)
Heating System
Provide explosion proof convection heater and interior mounted thermostats rated for Class I, Groups B, C, and D, Division I hazardous locations. Thermostat to have user adjustable temperature settings from 50° F to 90° F. The heater is to have a NEC Operating Temperature Code of T2A and rated for hazardous atmospheres with auto ignition temperatures at or above 536° F. UL Listed.
Explosion Proof Ventilation System
Ventilation system to include one enclosed explosion-proof motor (120 V, 4.5 A, 60 Hz, 1-phase) rated for Class I, Division I, Hazardous Locations with non-static and non-sparking cast aluminum fan blade to preclude the ignition of hazardous vapors. Interior fan to be constructed of heavy gauge steel. Interior exhaust vent to be located within 12 inches of the floor facilitating the extraction of heavier than air vapors. Ventilation system to shutdown automatically if fire occurs. Ventilation system to be activated by one exterior switch suitable for outdoor locations. Ventilation system to provide 1 cubic foot of exhaust ventilation per square foot of floor area. UL Listed.
Air Conditioning System
Provide explosion proof convection air conditioner rated for Class I, Groups B, C, and D, Division II hazardous locations. Air conditioning unit to be equipped with one interior thermostat bulb and one exterior temperature controller with user adjustable temperature setting from 70° F to 100° F. Protective coating to be applied to finned tube coils (evaporator and condenser), compressor and all other exposed surfaces. UL Listed