AG600 - 211.4 Cubic Ft; Dim: 8'4"H x 7'W x 5'D

Features & Specifications

Securall offers a complete line of safety storage buildings specifically designed for storing agri-chemicals and equipment safely. All buildings are designed to help you comply with safety rules when mixing and handling pesticides. These specially designed buildings are perfect for Golf Courses, Farms, Nurseries, Greenhouses and Landscape Contractors. Securall buildings help reduce the risk of poisoning and injuries among pesticide handlers and agricultural employees and will also help you protect against chemical spills, children and animal poisonings, theft, fire and unauthorized personnel.

Shelving & Lighting - Securall Agri-Chemical Storage lockers/buildings comes with 3 tiers of shelving. Interior & Exterior lighting, a receptacle and load center.

Easy To Ship Securall's Agri-Chemical Storage Buildings (AG1200 and Below) are designed to fit in a standard high cube shipping container reducing shipping costs and labor time.

Securall’s SMaRT Sustainable Certified products comply with Executive Order 13990 that mandates certified sustainable products. SECURALL’s SMaRT sustainable certified products reduce overall pollutants including toxic pollutants, acid rain, ozone depletors, water/air pollutants, and solid/hazardous waste.

Attributes

Approvals Complies with EPA & current OSHA regulations, UL - Include UL listed electrical accessories, FM-Factory Mutual Approved, NFPA - Designed in accordance with specifications set forth by the National Fire Protection Association
Dimension (H x W x D) 6'11"H x 5'W x 5'D
Limited 15 Year Warranty Yes
Quote Only Yes
Regulations Complies with EPA & current OSHA regulations, NFPA - Designed in accordance with specifications set forth by the National Fire Protection Association, UL - Include UL listed electrical accessories, FM-Factory Mutual Approved
Use Cases Chemical Storage Locker
Warranty 15 Year Structural Limited

Paint Color

The interior and exterior finish consists of an aliphatic polyurethane finish. This polyurethane coating has chemical properties to withstand salt spray, chemical rub, fading due to UV exposure, and other tests performed to epoxy paints. Urethane is more durable under conditions when moving items in and out of the cabinet as it resists chipping and peeling. Unless some other color is specified, cabinets will ship in designated standard color. For custom colors, customer must provide a paint chip.

Flammable & Combustible Classes

NFPA FLAMMABLE & COMBUSTIBLE CLASSES

FLAMMABLES FLASH POINT BOILING POINT
Class IA <73°F (22.8°C) <100°F (37.8°C)
Class IB <73°F (22.8°C) >=100° F
Class IC <73°F (22.8°C) and <100°F (37°C) >100° F

 

COMBUSTIBLES FLASH POINT BOILING POINT
Class II 100° F (37.8° C) ≤ FP < 140° F (60° C) -
Class IIIA 140° F (60° C) ≤ FP < 200° F (93° C) -
Class IIIB 200° F (93° C) ≤ FP -

9.5.1 The volume of Class I, Class II, and Class IIIA liquids stored in an individual storage cabinet shall not exceed 120 gal (460 L). 

9.5.2 The total aggregate volume of Class I, Class II, and Class IIIA liquids in a group of storage cabinets shall not exceed the maximum allowable quantity of flammable and combustible liquids per control area based on the occupancy where the cabinets are located.

* NFPA 30 Flammable and Combustible Liquids Code, 2011 Edition. Section 9.5.1, 9.5.2

FM Approved Fire Rating

Fire Rating According to FM

Securall Fire-Rated Storage Buildings (8'4"H X 42'W X 9'D Max Dimensions) carry the Factory Mutual System Approval label and have an FM Approved Fire Rated Wall & Roof Design. Wall and Roof are Tested at Intertek Testing Laboratories. Securall Fire-Rated Storage Buildings constructed based upon UL Fire Resistance Ratings classification criteria. Standard models are available in 2-hour and 4-hour fire ratings. Wall ratings are either 2 or 4 hour fire rated . Roof ratings are either 1.5 or 3 hour fire rated (Check with your local authority having jurisdiction for correct wall/roof rating needed). In addition, all Fire-Rated Buildings come with hydraulic operated self-closing, fire-rated doors and fire damper protected vents.

Industry's 1st & Only Intertek Tested and FM Approved 2 Hour Fire Rated wall construction built with 1.5 hour fire rated roof construction, 1.5 hour fire rated door construction, and multiple layers of ¾” gypsum ultracode wallboard. Air inlet vents with UL Listed and labeled fire damper with louvers. Dampers have a galvanized steel frame, curtain-type galvanized steel blades and a UL Listed 165° F fusible link.

Industry's 1st & Only Intertek Tested and FM Approved 4 Hour Fire Rated wall construction built with 3 hour fire rated roof construction, 3 hour fire rated door construction, and multiple layers of ¾” gypsum ultracode wallboard. Air inlet vents with UL Listed and labeled fire damper with louvers. Dampers have a galvanized steel frame, curtain-type galvanized steel blades and a UL Listed 165° F fusible link.

Please check with your local authority having jurisdiction for setback requirements and correct wall/roof rating needed.

Hurricane Resistant Wall Design

 

Securall Buildings have been tested to determine the amount of force they can withstand and were shown to withstand F-4 tornado force winds of 250 mph. The chart below demonstrates the wind speed that a particular length of wall will resist.

Upgrade package is available for Tornado Resistant Walls.

I B C wind speed

 

Securall Hazamat Storage Buildings are all-welded using 12 gauge (B/AG1600X-B/AG8000X Models) and 16 gauge (B/AG200X-B/AG1200X Models) galvannealed steel outer walls and 20 gauge cold rolled steel inner walls provide maximum durability, weather resistance, and rigidity.

Fire rated wall design