Vertical and Horizontal - DRUM STORAGE CABINETS |
Safe, convenient and centralized storage for Flammables. Vertical Cabinets have ball bearing rollers for easy placing and removal of 55 gallon drums. From one to twelve 5-gallon safety cans can also be stored depending on the model. Horizontal Cabinets store one 55 gallon drum and one 5 gallon safety can. Drum cradles available. Horizontal cabinets have tracks to guide Drum Cradle into position. Choose from 3 door styles. |
|
|
|
|
|
|
|
|
 |
|
| * Double wall construction with 1 ½” air space. |
| * Static grounding bolt Current OSHA compliant. |
| * Finished in 2-part urethane paint. |
| * Galvanized steel shelving. |
| * Two 2” vents with flash arrestors |
| * 3-point self-latching (Non Sparking) doors. |
| * Flush mounted locking handle. |
* Continuous piano hinge |
| * Leak proof sill 2” deep. |
* Large Warning label |
| * Reinforced 18-gauge all-welded construction |
| * Adjustable zinc plated leveling legs. |
|
CONTAINMENT CLASSIFICATIONS |
PAINT COLOR |
DOOR STYLE |
|
|
|
| |
NFPA FLAMMABLE & COMBUSTIBLE CLASSES |
| FLAMMABLES |
Flash Point |
Boiling Point |
| Class IA |
<73°F (22.8°C) |
<100°F (37.8°C) |
| Class IB |
<73°F (22.8°C) |
<100°F (37.8°C) |
| Class IC |
<73°F (22.8°C) and <100°F (37°C) |
- |
|
| |
COMBUSTABLES |
Flash Point |
Boiling Point |
| Class IIA |
<100°F (37.8°C) and <140°F (60°C) |
- |
| Class IIIB |
<140°F (60°C) and <200°F (93°C) |
- |
| Class IIIC |
<200°F (93°C) |
- |
|
| A maximum of 120 - gallons of Class I, Class II, and Class IIIA liquids may be stored in a single storage cabinet *. The number of cabinets in a single fire area may not exceed 3. Proper storage of additional cabinets within a single fire area is limited to groups no larger than 3, so long as a minimum of 100ft separation exists between all groups. The maximum number of cabinets in any one group may be increased to 6 if the cabinets are stored in an Industrial Occupancy facility that is equipped with an automatic sprinkler system meeting NFPA 13 standards for installation*. |
* NFPA 30 Flammable and Combustible Liquids Code, 2003 Edition. Section 6-6.3.1, 6.3.2, 6.3.4 |
|
|
|